If your control panel already contains a programmable logic controller (PLC) or pulse counter, a pulse-output energy meter can feed electricity usage data into that system. The meter sends out one signal per fixed unit of energy. The controller counts these signals and converts them into kilowatt-hours (kWh).

For equipment manufacturers, panel builders, and system integrators, the purchasing decision boils down to two checks: Can the input count every pulse at the highest expected load? Will the software convert that count into the correct kWh value? Confirm both before approving the meter for mass production.

Select Electrical Pulse Output for Your Controller

The meter may be equipped with a flashing LED, a wired pulse output, or both. The LED provides a visual signal for technicians. For wired PLC input, please ask the manufacturer to identify the output terminals and provide the electrical ratings and wiring diagrams for the specific model.

Saving Meter’s DTSU1218 three-phase DIN-rail energy meter features both LED and electrical pulse outputs, with an optocoupler output for active energy. If the project also requires connection for reading, Saving Meter’s 4G three-phase DIN-rail energy meter offers an active energy pulse output with a pulse width of 80 ms ± 20 ms. Please confirm the output rating and pulse constant for the version you are ordering.

Convert Pulse Counts to kWh

The pulse constant tells you how many pulses represent one kWh. A meter labeled 400 imp/kWh outputs 400 pulses for every kWh represented by that output.

For example, if the controller counts 2,000 pulses and the specified output corresponds to 400 pulses per measured kWh, the recorded energy consumption is 2,000 ÷ 400 = 5 kWh.

Saving Meter lists 400 and 6,400 imp/kWh on the product page for its DTSU1218 DIN-rail meter. Please confirm which value applies to the ordered configuration and wired output. For meters using current transformers (CT), also confirm whether the pulse value already represents primary-side energy. Apply any necessary multiplier once, at the agreed point in the system.

Check Pulse Timing Under Maximum Expected Load

A higher pulse constant provides more detailed data at low power consumption, but it also generates more pulses per second as the load increases. Therefore, a meter that works with a counter during a light-load test may still miss counts during full production.

For example, a 36 kW load at 400 pulses per kWh generates 4 pulses per second, with a steady load interval of approximately 250 ms between pulses. When performing this check, ensure the power and pulse constant are based on the same measurement basis. Then compare the expected pulse rate with the meter’s output limit and the controller’s input limits.

Confirm with the meter manufacturer Confirm with the controller supplier
Output circuit, voltage and current limits, and any external power supply requirements Input type and electrical compatibility
Pulse width range and maximum output rate Minimum acceptable pulse width and interval, input filter, and maximum counting rate
Which energy register the output represents and its scaling method Which edge is counted and how the counter scales to kWh

Determine Whether Pulse Counting Is Sufficient

Pulse counting may be appropriate for machines that only need running kWh totals or power consumption per shift. If operators also require voltage, current, or power factor readings, specify a separate data connection. The DTSU1218 product page also lists RS485 communication, supporting Modbus and DL/T 645. Confirm that the receiving system can read the required fields.

For equipment capable of returning power, please confirm whether the selected pulse output represents forward energy, reverse energy, or a combined value. A single-channel count alone does not provide direction information to the receiving system.

Approve Samples Before Bulk Purchase

Test the meter with the exact PLC input module and settings planned for production. Within a defined interval, compare the changes in the meter’s corresponding energy register with the kWh calculated from the pulse count. Repeat the test at a representative high load to check for missed or duplicate counts.

Next, restart the controller under controlled test conditions. Check whether it retains its total count and how the system flags any interval during which it was unable to count pulses. If the meter register is used to reconcile discrepancies, confirm that it represents the same energy and measurement boundary.

Once the sample passes, record the meter model, output terminals, pulse constant, controller settings, and test results. Use this record for repeat orders and unit replacements.

Request a Quote from Saving Meter

Jiangsu Saving Electronics Co., Ltd. manufactures electric meters and provides data acquisition equipment and system integration services. To request a quote, please provide your power supply voltage, phase and wiring configuration, current range, CT details (if used), maximum expected load, PLC input model, and order quantity.

Include your required delivery date and request model-specific drawings and pulse output specifications. Contact Saving Meter for project quotations to confirm compatibility between the meter and input before finalizing panel design.